Normally open solenoid valve selection guide: pressure, flow and materials
Release Date:
2026-11-14
Author:
Kangleda New Energy
Abstract
Article overview
This guide explains how to select a normally open solenoid valve by evaluating pressure, flow, materials and fail-safe requirements. It is aimed at UK water, HVAC and OEM engineers who need to compare NO and NC configurations and specify the correct valve first time.
Table of contents
- 1. What is a normally open solenoid valve?
- 2. NO vs NC solenoid valve: understanding the key differences
- 3. Pressure and flow selection criteria
- 4. Material compatibility and body construction
- 5. BSP port sizing and coil voltage options
- 6. Fail-safe design and WRAS compliance
- 7. Step-by-step selection process
- 8. Frequently asked questions
What is a normally open solenoid valve?
A normally open solenoid valve is an electrically operated valve that remains open when de-energised and closes only when electrical current is applied to its coil. This behaviour is the opposite of the far more common normally closed configuration, and that single distinction determines where the valve should — and should not — be used.
In practical terms, a normally open solenoid valve relies on the electromagnetic force generated by its coil to push a plunger or pilot piston against the flow path, sealing it shut. Remove the current — whether intentionally or through a power failure — and a return spring drives the plunger back, restoring flow immediately. This makes it a true fail-safe open device.
The valve belongs to the broader family of solenoid valve types and operation that includes 2-way, 3-way and proportional configurations. Within that family, the 2-way normally open solenoid valve is the most widely specified NO variant in UK industrial and plumbing applications.
How the internal mechanism works
Inside a direct acting solenoid valve, the core (plunger) sits in the open position held by the spring. When the coil is energised, the magnetic field overcomes spring force and pulls the core upward — or in some orientations, pushes it down — to seal the orifice. The transition typically takes 10–50 ms. Pilot-operated variants use the line pressure differential to assist opening and closing, allowing smaller coils to control much larger port diameters.
Typical NO valve applications
Actual testing in field installations confirms that NO valves excel wherever uninterrupted flow is the safe default. Common examples include emergency cooling circuits that must stay open if control power is lost, gas burner pilots where fuel must flow during ignition before the safety circuit confirms flame, and agricultural irrigation systems that default to watering during a controller fault rather than stressing crops. HVAC chiller bypass lines are another classic case: the system stays protected even during a panel outage.

NO vs NC solenoid valve: understanding the key differences
The choice between a normally open and a normally closed solenoid valve is fundamentally a fail-safe decision, not a preference. Get it wrong and a power interruption either floods a space or starves a process — both potentially damaging outcomes.
Electrical duty cycle implications
Here is a point many engineers overlook: an NO valve consumes power only when it needs to close. If your process runs in the open state for 90% of its cycle, the coil is energised for just 10% of the time. This reduces heat generation in the solenoid valve coil, extends coil life and lowers energy consumption. Conversely, a normally closed solenoid valve in the same application would draw continuous power, run hotter and risk coil burnout in poorly ventilated enclosures — a real concern in compact OEM assemblies.
Comparison table: NO vs NC solenoid valve
| Parameter | Normally open (NO) | Normally closed (NC) |
|---|---|---|
| De-energised state | Open (flow passes) | Closed (flow blocked) |
| Energised state | Closed (flow blocked) | Open (flow passes) |
| Fail-safe on power loss | Flow resumes (safe open) | Flow stops (safe closed) |
| Coil duty if process mostly open | Low (coil off when open) | High (coil on when open) |
| Typical UK applications | Cooling, irrigation, gas pilot | Water supply, chemical dosing |
| Minimum operating pressure (pilot-operated) | 0.5 bar (typical) | 0.5 bar (typical) |
| Direct acting option (zero pressure) | Available | Available |
"Specifying the wrong default state is the single most common solenoid valve selection error seen in UK industrial maintenance surveys. Always define what must happen on power loss before choosing between NO and NC." — Industrial Fluid Controls Best Practice Review, 2026
Pressure and flow selection criteria
Once the fail-safe state is confirmed, pressure and flow parameters become the two most critical technical filters. Undersize the flow coefficient and you create a throttling restriction; overrate the pressure and you overpay without benefit.
Understanding Kv: the flow coefficient
The Kv value expresses the volume of water (in m³/h) that flows through a fully open valve at a 1 bar pressure drop. It is the primary flow sizing parameter used across European valve standards. For a typical 1/2" BSP industrial flow control valve, Kv values range from 0.8 to 4.5 m³/h depending on orifice diameter and internal geometry. As a rule, always select a valve whose Kv exceeds your calculated system requirement by at least 15–20% to account for line losses and fluid viscosity variation.
Pressure rating and differential pressure
Pressure selection involves two distinct values: the maximum operating pressure (MOP) and the minimum differential pressure (MDP). Pilot-operated valves require a pressure differential across the orifice — typically 0.5 bar minimum — to assist actuation. A direct acting solenoid valve operates from zero differential pressure, making it essential for gravity-fed or low-pressure systems such as rainwater harvesting tanks common in UK sustainable building projects.
Most industrial electromagnetic valves for water carry a 10 bar MOP rating, while brass-bodied valves for steam can reach 15 bar. For compressed air and pneumatic solenoid valve applications, 10 bar ratings are standard, though some manifold-mount versions extend to 16 bar. Never operate a valve above its rated pressure — even briefly during surge events — as this stresses the diaphragm or piston seal and leads to premature failure.
Material compatibility and body construction
Material selection is where many solenoid valve selections go wrong — not because engineers choose the cheapest option, but because fluid compatibility is underestimated. The body material, seal elastomer and internal wetted components all need to suit the specific fluid, temperature and chemical environment.
Body material options
Brass remains the dominant body material for UK water solenoid valve applications. It is compatible with cold and hot potable water, compressed air and many light oils, and it machines cleanly for BSP threading. However, brass is unsuitable for demineralised water (which leaches zinc), seawater and many aggressive chemicals. Stainless steel (304 or 316L) handles these applications and also suits food-grade and pharmaceutical processes where hygiene validation is required. Polypropylene and PVDF bodies are preferred for aggressive acids and alkalis in chemical dosing systems — real-world installations confirm these materials outperform metal alternatives where pH falls below 4 or rises above 10.
Seal elastomer compatibility table
| Elastomer | Suitable fluids | Not suitable for | Max. temperature |
|---|---|---|---|
| NBR (Nitrile) | Water, air, mineral oils, fuels | Ozone, ketones, brake fluids | 90 °C |
| EPDM | Hot water, steam, acids, alkalis | Mineral oils, fuels | 150 °C |
| FKM (Viton) | Fuels, solvents, high-temp fluids | Ketones, low-temp applications | 200 °C |
| PTFE | Aggressive chemicals, acids | Dynamic high-cycle sealing | 200 °C |
| Silicone | Food, beverages, clean water | Petroleum products, solvents | 180 °C |
Of course, there are situations where even a correctly specified elastomer degrades faster than expected — particularly when fluid temperature cycles rapidly or trace contaminants are present. When in doubt, request a material compatibility confirmation from the valve supplier before final procurement.
BSP port sizing and coil voltage options
In the UK market, British Standard Pipe (BSP) threads are the dominant connection standard for plumbing and industrial fluid systems. Matching port size to your pipework is straightforward — but selecting the correct orifice diameter within a given port size requires the Kv calculation described above.
Standard BSP sizing reference
| BSP port size | Orifice diameter range | Typical Kv (m³/h) | Common application |
|---|---|---|---|
| 1/8" BSP | 1.5–3 mm | 0.08–0.25 | Pilot lines, instruments |
| 1/4" BSP | 3–6 mm | 0.25–0.8 | Coffee machines, lab equipment |
| 3/8" BSP | 6–10 mm | 0.8–2.0 | Domestic appliances, irrigation |
| 1/2" BSP | 10–15 mm | 2.0–4.5 | HVAC, general plumbing |
| 3/4" BSP | 15–20 mm | 4.5–9.0 | Industrial cooling, process |
| 1" BSP | 20–25 mm | 9.0–18.0 | Large-scale water systems |
Coil voltage: AC vs DC and UK standards
UK mains voltage is 230 V AC at 50 Hz, so 230 V AC coils are the standard choice for panel-powered industrial applications. Where 24 V DC control systems are used — typical in modern PLC-based plant and OEM machinery — a 24 V DC coil is specified. The solenoid valve wiring connection is usually a standard DIN 43650A (Form A) plug connector, which accepts flying lead or plug-in coil connections and simplifies field replacement.
Why does AC vs DC matter beyond voltage? AC coils generate more heat due to inrush current during energisation and require an internal shading ring to prevent buzzing. DC coils run quieter and cooler but need a stable regulated supply. For intermittent-duty NO valve applications, a DC coil with a rectifier-equipped plug often provides the best balance of quiet operation and longevity.
Fail-safe design and WRAS compliance
The fail-safe characteristic of an NO valve is both its defining advantage and a responsibility. Correctly applied, it protects systems and processes during power loss. Incorrectly applied, it can cause flooding, overpressure or uncontrolled fluid release — outcomes that are both costly and potentially hazardous.
Defining the failure mode correctly
Industry consensus is clear: before specifying any de-energised open valve, the design engineer must document the worst-case consequence of power loss with the valve open. For a cooling water supply to a heat exchanger, flow on power loss is benign. For a dosing valve feeding a chemical into a process vessel, uncontrolled flow could be dangerous. In the latter case, a normally closed solenoid valve is the correct choice, regardless of duty cycle efficiency arguments.
WRAS approval for UK potable water
Any water solenoid valve used in UK potable water systems must carry WRAS (Water Regulations Advisory Scheme) approval. WRAS-approved valves have been independently tested to confirm that wetted materials do not leach substances into drinking water above permitted thresholds. This requirement applies to both the body material and all elastomers in contact with the water supply. Specifying a non-WRAS valve in a potable water application is a compliance failure that building regulations inspectors and water utility contractors will reject. Always request the WRAS approval certificate and listing number at the procurement stage.
ATEX-rated solenoid valves are additionally required in hazardous area applications — for example, natural gas pilot systems or solvent handling in Zone 1 or Zone 2 classified areas. The ATEX marking must match the zone classification and equipment group of the installation.
Step-by-step selection process
Following a structured sequence eliminates the most common specification errors. Think of it like a diagnostic checklist — skipping steps is where problems arise.
The seven-step selection checklist
- Define the fail-safe state. Ask: what must happen to fluid flow if power is lost? If flow must continue, specify an NO valve. If flow must stop, specify an NC valve.
- Identify the fluid. Record fluid type, temperature range, viscosity and any chemical composition relevant to material compatibility.
- Establish pressure parameters. Confirm maximum operating pressure, minimum differential pressure and whether the system can support pilot-operated actuation (≥0.5 bar DP) or requires a direct acting solenoid valve (zero DP).
- Calculate required Kv. Use the formula Kv = Q / √ΔP (where Q is flow in m³/h and ΔP is pressure drop in bar) and add a 15–20% safety margin.
- Select body material and seal elastomer. Cross-reference fluid and temperature against the compatibility table. Confirm WRAS approval if the application involves potable water.
- Choose BSP port size. Match the calculated Kv requirement to the port and orifice size reference table. Select the smallest port size that meets the Kv requirement to minimise cost and installation space.
- Specify coil voltage and protection rating. Confirm supply voltage (230 V AC or 24 V DC), DIN connector type and IP rating. IP65 is minimum for most industrial environments; IP67 or IP68 for submerged or wash-down applications.
Common selection mistakes to avoid
Based on real-world cases, the most frequent errors are: selecting pilot-operated valves for low-pressure systems (the valve refuses to open fully), ignoring fluid temperature when specifying NBR seals in hot-water circuits (premature seal swelling and leakage), and failing to verify WRAS approval status before installation. A second common trap is assuming that a larger port always gives better flow — orifice diameter within the port body matters more than the thread size on its own.
The normally open solenoid valve, when correctly specified using this methodology, is a reliable, low-maintenance component that can deliver millions of operating cycles. When misspecified, it becomes a recurring maintenance liability. The structured approach above removes ambiguity and gives procurement teams a defensible technical record for every valve selection decision.
Frequently asked questions
Q: What does "normally open" mean on a solenoid valve?
A: "Normally open" means the valve allows fluid flow in its default, de-energised state. When electrical current is applied to the coil, the valve closes and blocks flow. This configuration is chosen when the fail-safe requirement is for flow to continue during a power failure.
Q: Can I use a normally open solenoid valve on a mains water supply?
A: Yes, provided the valve carries WRAS approval for potable water contact. Confirm that both the body material and seal elastomers are listed in the WRAS approval certificate. Standard brass-bodied, NBR-sealed NO valves are widely WRAS-approved for cold and hot potable water up to 90 °C.
Q: What is the difference between direct acting and pilot-operated NO valves?
A: A direct acting solenoid valve uses only electromagnetic force to open and close, working from zero differential pressure. A pilot-operated valve uses line pressure to assist actuation and requires a minimum of around 0.5 bar differential pressure. Direct acting valves suit low-pressure and gravity-fed systems; pilot-operated valves are preferred for larger port sizes at higher pressures.
Q: How do I calculate the correct Kv for my application?
A: Use the formula Kv = Q ÷ √ΔP, where Q is your required flow rate in m³/h and ΔP is the allowable pressure drop across the valve in bar. Always add a 15–20% margin above the calculated value and cross-reference the result against the manufacturer's Kv specification for the port size you are considering.
Q: Is a normally open solenoid valve suitable for compressed air systems?
A: Yes. Pneumatic solenoid valve variants in NO configuration are commonly used in compressed air systems, particularly for cylinder return circuits and emergency exhaust functions. Specify NBR seals for standard dry air, verify the maximum operating pressure matches your system (typically 10–16 bar) and confirm the IP rating suits the installation environment.